Features and Specifications
20 ONePlus UPS User Instruction Manual
Physical and
Electrical
Specifications
Surge voltage withstand capability:
ANSI/IEEE
C62.41 Category A&B, 6 kV/ 200 & 500 Amp, 100
kHz ringwave
Surge voltage let-through (max): Less than 10 V
Normal mode (L-N), less than 0.5V Common mode
(N-G) when subjected to 6 kV ANSI/IEEE C62.41
Cat. A
Normal & common mode clamping response
time: Instantaneous
Transfer time (max): <6 milliseconds
On battery output voltage: Sine wave
Buck and Boost: maintains output voltage between
101 and 132 VAC while input voltage varies between
89 and 152 VAC.
Load power factor range (crest factor): UPS .65 to
1.0 (3)
Batteries: Sealed, maintenance-free lead acid with a
2-4 year typical lifetime, user replaceable
Recharge time to 90% available capacity: 3-6
hours after full discharge to cut off