Features and Specifications
22 ONePlus UPS User Instruction Manual
Operating Elevation 0 to 3,000 m (0 to 10,000 ft.)
Storage Elevation 0 to 15,000 m (0 to 50,000 ft.)
UPS Dimensions(HxWxL) in.
(HxWxL) (cm)
7.1 x 5.5x 13.8 7.1 x 5.5x 15.4 9.3 x 7.1 x 15.0 9.3 x 7.1 x 15.0
(18 x 14 x 35) (18 x 14 x 35) (23.5 x 18 x 38) (23.5 x 18 x 38)
UPS Shipping Weights lbs. (kg) 28 (12.7) 28.6 (13) 57 (25.7) 63 (28.5)
Surge Voltage Withstand Capability
ANSI/IEEE C62.41 Category A&B, 6kV/200 &500 Amp, 100kHz
Ringwave
Surge Voltage Let-through
Less than 10V normal mode (L-N), less than 0.5 V Common mode (N-G)
when subjected to ANSI/IEEE C62.41 Cat. A
Normal & Common Mode Clamping
Response Time
instantaneous
* “T-slot” output connector will accept either 5-15P or 5-20P plugs
** ONePlus UPS should be operated or stored in locations where ambient temperature does not exceed 25°C
(77°F) to preserve optimal battery life.
Table 2. Physical/Electrical Specifications and Performance Characteristics
Specification and Characteristics ONePlus250 ONePlus400 ONePlus600 ONePlus1000