Enter the correct password, then follow the instructions for changing a value as
specified on page p. 41. The default Level 1 password is “1234”.
If the wrong password is entered, the message “Wrong Password” will display and
then return to the programming entry screen.
Main Menu
If the password is accepted, the Main Menu screen will be shown:
F1 F2 F3 F4
This is the Main Menu screen for the programming mode.
Press EXIT (F4) repeatedly until “Normal Mode” is seen briefly to exit the programming
mode.
Analog 4-20mA Output
The following menu allows the scaling of the analog 4-20mA output.
From the Main Menu, press I/O (F1) to move to the 4-20mA output selection.
In this screen press 420 (F3) (screen appearance may vary according to options).
F1 F2 F3 F4
The 4-20mA output is programmable for flow or temperature:
F1 F2 F3 F4
Selections for the 4-20mA output are:
Flow
Temp
Select NXT (F1) to select Flow or Temperature and then press OK (F4).
F1 F2 F3 F4
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com
F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page 42
Model F-5500
OPERATION
Operation: Programming
Programming
by Display
Analog
4-20mA Output
Main Menu
MAIN MENU
I/O FLO DSP EXIT
mA=Flow
NXT OK
20 mA = 3500 SCFM
CHG OK
SET I/O
COM PUL 420 EXIT