F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page 68
Model F-5500
COMMUNICATIONS
Model F-5500
COMMUNICATIONS
Modbus Programming
Modbus
Communication
Parameters
i
BACnet
Introduction
Selections are: "115200"
"57600"
"38400"
“19200”
“9600”
“4800”
“2400”
“1200”
F1 F2 F3 F4
Press NXT (F1) repeatedly until the correct selection is shown and then press OK (F4)
to accept the setting.
Selections are: “NONE”
“ODD”
“EVEN”
F1 F2 F3 F4
Press CHG (F1) to change the address and then press OK (F4) to accept the setting.
Selections are between 01 and 247.
NOTE: Power cycle is required for the new settings to take effect.
Parity=EVEN
NXT OK
Address=02
CHG OK