F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page 70
Model F-5500
COMMUNICATIONS
Model F-5500
COMMUNICATIONS
BACnet Protocol
Device object property identifiers and restrictions: (properties that are writable)
Object _Name < 10 bytes
Object _ Identifier Device Type only
Max _ info_ Frames <=255
Max _ Master <=127
BACnet Interoperability Building Blocks (BIBB’S) provide function capabilities for data
exchange between devices.
F-5500 BIBB’s supported:
DS-RP-B Read Property
DS-WP-B Write Property
DM-DDB-B Dynamic Device Binding
DM-DOB-B Dynamic Object Binding
DM-DCC-B Device Communication Control
DS-RPM-B ReadPropertyMultiple
DM-RD-B Reinitialize Device
MS/TP baud rates:
9600, 19200, 38400, 57600, 76800, 115200
F-5500 Character sets supported:
ANSI X3.4, UTF-8
ONICON BACnet vendor ID: 206
For more information about BACnet visit http://www.bacnet.org/.
Enter the Programming Mode - BACnet MS/TP
Press the F1 or the F2 key repeatedly, in the normal running mode, until the following
screen is shown. This enters the programming mode:
F1 F2 F3 F4
BACnet Protocol
BACnet
Programming
SET PARAMETERS?
NO YES
BACnet
Programming