F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page 71
Model F-5500
COMMUNICATIONS
Model F-5500
COMMUNICATIONS
BACnet
Programming
Press YES (F4) and then the following screen will prompt the user to enter the
password if enabled:
F1 F2 F3 F4
Enter the correct password. Default password for Level 1 is 1234.
Communication Protocol and Parameters
To program the communication parameters, press I/O (F1) key from the main menu.
F1 F2 F3 F4
This is the main menu for the programming mode. To exit the programming mode,
press EXIT (F4) repeatedly until “Normal Mode” is seen briefly. Choose I/O (F1) to
access the communication output.
F1 F2 F3 F4
Then press COM (F1) to select communication parameters
Set Bus protocol for BACnet:
F1 F2 F3 F4
Press NXT (F1) until BACnet is selected as shown and then press OK (F4) to accept
the setting.
F1 F2 F3 F4
Press NXT (F1) repeatedly until the correct selection is shown and then press OK (F4)
to accept the setting.
PASWD:_
UP DN NXT OK
MAIN MENU
I/O FLO DSP EXIT
BACnet Programming
SET I/O
COM 420 EXIT
Comm=BACnet
NXT OK
Baud=9600
NXT OK
BACnet
Communication
Parameters