F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023 Page 72
Model F-5500
COMMUNICATIONS
COMMUNICATIONS
BACnet Programming
BACnet
Communication
Parameters
Selections are: “9600”
“19200”
“38400”
“57600”
“76800”
“115200"
Next select the MS/TP Mac address. The selection is from 0-127. Please note
that only one device can be on a MS/TP Mac address.
F1 F2 F3 F4
Next select the MS/TP Max Master using CHG (F1). The selection is from
0-127. Press OK (F4) to accept the setting.
F1 F2 F3 F4
Next input the device object instance using CHG (F1). Selection is from
0-4194303. Press OK (F4) to accept the setting.
F1 F2 F3 F4
Next enter the device object name (9 characters maximum) using CHG (F1).
Press OK (F4) to accept the setting.
F1 F2 F3 F4
NOTE: Power cycle is required for the new settings to take effect.
i
MAC_ADD=23
CHG OK
NAME=F-5500_FLOW
CHG OK
ID=12531
CHG OK
MAX_MASTER=127
CHG OK