CurrentType Values
Maximum inrush current 60 Amps
Environmental Specications
Specication State British Metric
Temperature Operating (sea level) 41° F to 100° F 5° C to 35° C
Non-operating -40° F to 158° F -40° C to 70° C
Humidity Operating 10% to 93% RH
non-condensing, 80.6° F
max wet bulb
10%to 93% RH
non-condensing, 38° C
max wet bulb
Non-operating 93% RH, non-condensing,
100.4° F max wet bulb
93% RH, non-condensing,
43° C max wet bulb
Vibration Operating 0.12 G x-y, 0.17 G z;5-500
Hz sine
Non-operating 0.3 G x-y, 0.6 G z;5–500 Hz
sine
Shock Operating 3.5 G; 11 msec. half-sine
Maximum operating
temperature derating
-1.8° F for every 985 ft. in
altitude
-1° C for every 300 m in
altitude
Altitude Operating 0 to 10,000 feet 0 to 3,048 m
Acoustic Noise Specications
23° C Idle 23° C Operating
L
w
A
d
7.0 B 7.5 B
LpAm 60 dba 70 dba
Environmental Specications
Sun Fire X2270 M2 Server Service Manual • January, 2012, –1296