IG-123-EN version 11; 23/07/2021
35
General instructions
cpg.0: GIS medium-voltage switchgear,
gas insulated, up to 40.5 kV,
in accordance with IEC Standard
Installation
Continuation
Cubicle
model
Manu-
facturer
Connector
Connector
series
Nº
terminals
Terminal
conguration
Max. rated
current
connector
[A]
Total
connector
length
[mm]
Max. diameter
on insulation
admitted by
the connector
[mm]
cpg.0-f/
Nexans
EUROMOLD
Screened
400TB
1 cable 400TB + CUP 800 255 37.5
1 cable + SA
400TB + 400PB-10SA
+ CUP
800 410 37.5
440TB
1 cable 440TB + CUP 1250 255 56
1 cable + SA
440TB + 400PB-10SA
+ CUP
1250 410 56
480TB
1 cable 480TB + CUP 1250 185 40.5
1 cable + SA 480TB + 800SA + CUP 1250 290 40.5
484TB
1 cable 484TB + CUP 1250 185 56
1 cable + SA 484TB + 800SA + CUP 1250 290 56
cpg.0-vl,
cpg.0-
side bushing
Nexans
EUROMOLD
Screened
400TB 1 cable 400TB + CUP 800 255 37.5
440TB 1 cable 440TB + CUP 1250 255 56
480TB
1 cable 480TB + CUP 1250 185 40.5
2 cables 480TB + 804PB + CUP 1250 295 40.5
484TB
1 cable 484TB + CUP 1250 185 56
2 cables 484TB + 804PB + CUP 1250 295 56
Table 6.3. Recommended connectors