IG-123-EN version 11; 23/07/2021
53
General instructions
cpg.0: GIS medium-voltage switchgear,
gas insulated, up to 40.5 kV,
in accordance with IEC Standard
Operations sequence
2. Push the handle forward rmly to move the
disconnector to "connected" position.
Figure 7.43. Disconnector displaced to "connected" position cpg.0-v 36
kV/1250 A/25 kA
Figure 7.44. Disconnector displaced to "connected" position cpg.0-v 12
kV/2000 A/25 kA
3. Move the locking lever up as far as it will go to lock the
mechanism in "connected" position.
Figure 7.45. Mechanism locking in "connected" position cpg.0-v 36
kV/1250 A/25 kA
Figure 7.46. Mechanism locking in "connected" position cpg.0-v 12
kV/2500 A/25 kA