EasyManua.ls Logo

PACSystems RX3i - Page 20

PACSystems RX3i
87 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual Chapter 1
GFK-2749A Jan 2020
PSM Module Description and Specifications 16
mover power rises above the REV_PWR_THR for a time period longer than REV_PWR_
DELAY. The REV_PWR_THR is a percentage of the nominal power which, in a 3-phase
system, is three times the nominal voltage multiplied by the nominal current.
ANSI 47 Voltage Phase Sequence Protection
The sequence of the phase A, B and C voltages is monitored. Detection of a wrong sequence
(A, C, B for example) will trigger an alarm.
ANSI 50 Instantaneous Over-current Protection
Provides three-phase protection against overloads and phase-to-phase short-circuits. The
alarm will be triggered if any phase current exceeds the specified OVER_CURR_ THR voltage
value for a time period longer than OVER_CURR_DELAY. The OVER_CURR_THR is a
percentage of the nominal current.
ANSI 59 Over-voltage Protection
This provides detection of abnormally high phase voltage. It works with phase-to-phase
voltage in Delta power systems, or phase-to-neutral voltage in WYE Power systems. Each
voltage is monitored separately. An alarm will be triggered if any voltage exceeds the
specified OVER_VOLT_THR value, as a percentage of the Nominal Voltage parameter, for a
time period longer than OVER_VOLT_DELAY. This alarm is cleared when the voltage drops
below the OVER_VOLT_THR value for a time period longer than the OVER_VOLT_DELAY.
The OVER_VOLT_THR is a percentage of the nominal voltage.
ANSI 60 Voltage (current) Imbalance
An alarm will be triggered if any phase voltage or current reading varies from the average of
all three phases by more than VI_IMBALANCE_THR for a time period longer than
VI_IMBALANCE_DELAY. The alarm is cleared when the imbalance condition is corrected for
a time period longer than VI_IMBALANCE_DELAY. IV_IMBALANCE_THR is a percentage of
the average of the three phase voltages (for voltage imbalance) or the three phase currents
(for current imbalance) on a given grid. It works with phase-to-phase voltage in Delta power
systems, or phase-to-neutral voltage in WYE Power systems. No comparison is performed
between the two grids. Neutral current is not monitored for imbalance.
ANSI 81U Under-frequency Protection
Detection of abnormally low frequency compared to the nominal frequency, to monitor
power supply quality. An alarm will be triggered if a circuit’s frequency falls below the
nominal frequency minus the UNDER_FRQ_THR for a time period longer than
UNDER_FRQ_DELAY. The alarm is cleared when the frequency rises above the nominal
frequency minus UNDER_FRQ_THR for a time period longer than UNDER_FRQ_DELAY.
UNDER_FREQ_THR is an absolute frequency, in Hz, that is subtracted from the nominal
frequency to determine the lowest acceptable frequency for the grid.

Table of Contents

Other manuals for PACSystems RX3i