EasyManua.ls Logo

PACSystems RX3i - Environmental Specifications

PACSystems RX3i
87 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual Appendix A
GFK-2749A Jan 2020
Product Certifications and Installation Guidelines for Conformance 81
Description
Agency
Standard or
Marking
Comments
Explosive Atmospheres Directive
European Safety for Hazardous
Areas Equipment Group II,
Category 3, Gas Groups A, B, C
Certification in accordance with European
Directives and Independent 3rd Party
Assessment Certificate; Refer to Declaration
of Conformity found at
http://www.Emerson.com/Industrial-
Automation-Controls
for complete list of approved products
Note: The agency approvals listed above and on the Declaration of Conformities are believed to be
accurate; however, a product’s agency approvals should be verified by the marking on the
unit itself.
A.2 Environmental Specifications
Vibration
IEC60068-2-6, JISC0911
10 - 57 Hz, 0.006" displacement
peak- peak 57 - 500 Hz, 1.0g
acceleration
Shock
IEC60068-2-27, JISC0912
15G, 11ms
Operating Temperature
0°C to 60°C: [surrounding air] (32° F to 140°F)
Storage Temperature
-40°C to +85°C (-40° F to 185°F)
Humidity
5% to 95%, non-condensing
EMC Emissions
Radiated, Conducted
CISPR 11/EN 55011/
EN55016-2-3
47 CFR 15
Group 1, Class A
30 230 Mhz 50.4 dBuV/m
230 1000 Mhz 57.4 dBuV/m
30 88 Mhz 49.5 dBuV/m
88 216 Mhz 53.9 dBuV/m
216 -960 Mhz 56.8 dBuV/m
> 960Mhz 59.9 dBuV/m
EMC Immunity
[applies to CE Marked modules]
EMC Requirements & Test for
Programmable Controllers
EN 61131-2
Zone B
Electrostatic Discharge
EN 61000-4-2
1
8KV Air, 4KV Contact
RF Susceptibility
EN 61000-4-3
1
10 Vrms /m:
3 Vrms/m :
1 Vrms/m:
0.80 -1.0GHz,
1.4 - 2.0GHz
2.0 - 2.7Ghz
Fast Transient Burst2
EN 61000-4-4
1
Unshielded I/O Signal: 1KV

Table of Contents

Other manuals for PACSystems RX3i