User Manual Chapter 2
GFK-2749A Jan 2020
Installation 18
Chapter 2: Installation
2.1 General Warnings/Cautions
WARNING
Installation and wiring procedures must be performed by qualified personnel, as defined
below.
Qualified personnel are people who, because of their education, experience and instruction
and their knowledge of relevant standards, regulations, accident prevention and service
conditions, have been authorized by those responsible for the safety of the plant to carry
out any required operations and who are able to recognize and avoid any possible dangers.
(Definitions for skilled workers according to EN50110-1.)
WARNING
HIGH VOLTAGE; HIGH CURRENT
DO NOT TOUCH the connectors or wiring after powering up the PSM system. Hazardous
voltages exist, and death or injury may result.
The Terminal Assembly frame ground connection must always be installed and must be
installed before any other wiring is attached.
To reduce risk of electric shock or damage to the attached CTs, always open or disconnect
all voltage circuits and apply the shorting bar connections to the current inputs before
installing or servicing the connections to the Terminal Assembly.
Never disconnect the GRID 1 or GRID 2 field wiring while power is present. Personal injury or
equipment damage may result. Finger guards must be installed on the Terminal Assembly
before energizing the field wiring.