EasyManua.ls Logo

PACSystems RX3i - Page 47

PACSystems RX3i
87 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual Chapter 3
GFK-2749A Jan 2020
Configuration and Data Transfer 43
Offset
Definition
Value
Status/Alarm
Timing
A, B, AB: See
Status/Alar
m Timing
on page 45
Alarm
3
Availability
21
GRID 1 FaultVA/VBA;
VB/VAC; VC/VBC
A
22
GRID 1 FaultIC
A
23
GRID 1 FaultIN
A
24-32
Reserved
33
GRID 2 FaultVA_VCA
0 = OK
1 = Fault clamped or
not calculated/measured
A
34
GRID 2 FaultIA
A
35
GRID 2 FaultVB_VCB
A
36
GRID 2 FaultIB:
A
37
GRID 2 FaultVC:
A
38
GRID 2 FaultIC
A
39
GRID 2 FaultIN
A
40 - 48
Reserved
49
GRID 1 ClampedFreq
0 = OK
1 = Line Frequency
outside the range (30 -
70 Hz)
A
50
GRID 1 ClampedInput:
0 = OK
1 = some inputs have
signal clamped
A
51
GRID 1 MixedPolarity
0 = OK
1 = At least one phase
PT/CT has wrong polarity
B
52
GRID 1 VoltPhSeqAlarm
0 = OK
1 = ANSI 47 Alarm
B
53
GRID 1 UnderVoltAlarm
0 = OK
1 = ANSI 27 Alarm
B
54
GRID 1 ReversPwrAlarm
0 = OK
1 = ANSI 32 Alarm
B

Table of Contents

Other manuals for PACSystems RX3i