12.  Operation Control 
12.1  Basic Function 
12.1.1  Internal Setting Temperature 
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting 
processes. These shifting processes are depending on the air conditioner settings and the operation environment. 
The final shifted value will be used as internal setting temperature and it is updated continuously whenever the 
electrical power is supplied to the unit. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
12.1.2  Cooling Operation  
12.1.2.1  Thermostat control 
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5℃ 
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > 
Compressor OFF point +0.5K. 
 
12.1.3  Soft Dry Operation 
12.1.3.1  Thermostat control 
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.5℃ 
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > 
Compressor OFF point +0.5K. 
Remote Control Setting Temp. (16℃~30℃) 
Auto operation Mode Shifting