15.4.18 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)
Malfunction Decision Conditions
Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C)
Malfunction Caused
Clogged air filter of the indoor unit.
Dust accumulation on the indoor unit heat exchanger.
Air short circuit.
Detection error due to faulty indoor pipe temperature sensor.
Detection error due to faulty indoor unit PCB.
Troubleshooting
Check the air passage
When abnormality indication starts again
Is there any short circuit?
YES
YES
YES
YES
NO
Check the air filter
Is the air filter dirty?
Is the indoor unit heat exchanger dirty?
Does it conform to the sensor characteristic chart?
Check the dust accumulation on the indoor unit heat
exchanger
Check the indoor heat exchanger temperature
sensor
Provide sufficient air passage
Clean the air filter
Clean the indoor unit heat
exchanger
Defect in indoor unit PCB
Replace the indoor unit PCB
Replace the indoor unit PCB
NO
NO
NO
For safety reason and to prevent
component breakdown, always switch
off the power before remove and
connect the component.
Caution

Table of Contents

Other manuals for Panasonic CS-S18TKV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-S18TKV and is the answer not in the manual?

Panasonic CS-S18TKV Specifications

General IconGeneral
BrandPanasonic
ModelCS-S18TKV
CategoryAir Conditioner
LanguageEnglish

Related product manuals