Error reset method
Press “OFF/ON” button to OFF the operation.
Press AUTO OFF/ON button at indoor unit to OFF the operation.
OFF Timer activates.
Power supply reset.
o nanoe-G breakdown error
Judgment method
Hi-feedback voltage (at microcontroller) supplied to the nanoe-G system when nanoe-G operation is
OFF; nanoe-G breakdown error show immediately.
It is due to indoor PCB or nanoe-G high voltage power supply damage.
Operations except nanoe-G continue. Both Timer indicator and nanoe-G indicator blink.
Troubleshooting method
Press nanoe-G button or OFF/ON button to stop the operation.
Change nanoe-G high voltage power supply or main PCB.
When Lo-feedback voltage supplied to nanoe-G system during nanoe-G operation ON, nanoe-G
indicator and Timer indicator stop blinking.
12.11 In-filter Deactivation Operation
This operation helps to deactivate virus and bacteria on filter after the unit turned off using nanoe-G generator.
In-filter deactivation start condition
o nanoe-G is in ON condition before the unit is turned off either by OFF/ON button or OFF Timer.
o Elapsed time from previous in-filter deactivation operation is more than 24 hrs.
o Unit operation time before unit is turned off is more than 2 hours or accumulated unit operation time achieves
4hrs if unit operation time less than 2 hours.
In-filter deactivation stop condition
o The unit is turned on.
o nanoe-G generator operation time during in-filter deactivation operation has achieved 120 minutes.
o The unit received disable signal from remote control.
o Nanoe-G abnormality occurs.
Control contents:
o When the unit operate in Cool or Dry mode before turned off.
1. The unit will operate fan operation, fan motor will operate at 500 rpm for 30 minutes then stop.
2. During fan operation, horizontal vane will fixed at 30° (outer vane) and 63° (inner vane) for 30 minutes
then close.
3. After 30 minutes the unit will continue with common control.
o Common control.
- nanoe-G generator will operate for 120 minutes.
Timer control
o When ON Timer activates during in filter deactivation operation, in-filter deactivation operation stops.
o When OFF Timer activates during in filter deactivation operation, in-filter operation will continue.
Indicator
o nanoe-G indicator ON.
o Power indicator OFF.

Table of Contents

Other manuals for Panasonic CS-S18TKV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-S18TKV and is the answer not in the manual?

Panasonic CS-S18TKV Specifications

General IconGeneral
BrandPanasonic
ModelCS-S18TKV
CategoryAir Conditioner
LanguageEnglish

Related product manuals