12.12.1.9 Rhythmic Temperature Wave Operation
To further maximize the energy saving during ECONAVI operates at low activity level.
Start condition
o The unit is operates in Cool or Dry mode under ECONAVI operation, and
o Human activity sensor detects low activity level continuously for 60 minutes, and
Stop condition
o Unit is off, or
o ECONAVI is off, or
o Human activity sensor detects high activity level or absent, or
Control contents
o When all start conditions complied, set temperature will shift accordingly as following:
ECONAVI
Mode
Human
Low activity Normal activity High activity Absent
COOL/DRY
Set
temperature
ECONAVI
Precise control of temperature during low activity to
maximise energy saving.
Mode Human Low activity
COOL/DRY
Set
temperature
+1°C /
+2°F
+2°C /
+4°F