96
Diagnosis
display
Abnormality / Protection
control
Abnormality
Judgment
Protection
Operation
Problem Check location
F93
Compressor abnormal
revolution
4 times happen
within 20 minutes
—
Compressor abnormal
revolution
Power transistor module
faulty or compressor lock
F95
Outdoor cooling high pressure
protection
4 times happen
within 20 minutes
—
Cooling high pressure
protection
Check refrigeration system
Outdoor air circuit
F96
Power transistor module
overheating protection
4 times happen
within 30 minutes
—
Power transistor module
overheat
PCB faulty
Outdoor air circuit (fan motor)
F97
Compressor overheating
protection
3 times happen
within 30 minutes
— Compressor overheat
Insufficient refrigerant
F98
Total running current
protection
3 times happen
within 20 minutes
— Total current protection
Check refrigeration system
Power source or compressor
lock
F99
Outdoor direct current (DC)
peak detection
Continuous happen
for 7 times
—
Power transistor module
current protection
Power transistor module
faulty or compressor lock
Note:
“○” – Frequency measured and fan speed fixed.
“ * ” – For cooling only model, it is the indication when indoor heat exchanger sensor or indoor air intake sensor has
abnormality.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep”
sound heard following by pressing the CHECK button at remote control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors
(refer to Error Code Table) by using remote control or Auto OFF/ON button at indoor unit. However, the remote
control signal receiving sound is changed from one “beep” to four “beep” sounds.