14.14    Odor Cut Control 
  To reduce the odor released from the unit.  
o  Start condition 
  AUTO FAN Speed is selected during COOL or DRY operation. 
  During freeze prevention control and timer preliminary operation, this control is not applicable. 
o  Control content 
  Depends on compressor conditions: 
1.  Compressor OFF → Compressor ON. 
The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 50 seconds. 
2.  Compressor ON → Compressor OFF. 
The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds.