890CD Power Connections 
 
 
 
•  Connect motor leads to M1, M2, M3. 
Maximum wire sizes: 
Frame B: 4mm
2
/12AWG 
Frame C: 10mm
2
/8AWG 
Frame D: 16mm
2
/4AWG 
•  Connect the earth/ground wire from the terminal 
box of the motor directly to the bottom ground 
bracket. 
Maximum wire sizes: 
Frame B: 4mm
2
/12AWG 
Frame C: 10mm
2
/8AWG 
Frame D: 16mm
2
/4AWG 
•  If not using shielded cable, run motor leads in an 
enclosed metal conduit grounded at both ends 
4 
•  Connect the earth/ground wire to the 
bottom ground bracket. 
Maximum wire sizes:  
Frame B: 4mm
2
/12AWG 
Frame C: 10mm
2
/8AWG 
Frame D: 16mm
2
/4AWG 
5 
•  Connect motor thermal switch or thermistor to 
Th1, Th2. Drive will trip when the thermal switch 
opens, or when the thermistor resistance 
exceeds 4kΩ maximum (PTC Type A : IEC 34-11 
Part 2) 
•  If the motor does not have a protective device 
(thermistor), jumper these terminals. The drive 
needs the thermistor inputs connected for it to 
run. 
6 
•  Connect the 24V DC brake supply to terminals 1 
and 2, and connect the brake terminals to 3 and 
4. The brake coil is energized when the drive 
runs.  