Pilot Operated Prop. DC Valve with VCD
®
Series D*1FP/FE Explosion Proof
Operation Manual
Parker Hannifin Corporation
MSG11-5715-718 D_1FP IECEX UK.indd 19.12.19
Parameter Description Unit
Parameter Range
Default
Setting
Comment
from up to
J8
Min supply voltage
supervision
V 17 28 18
J9
Relay time out off range
min supply voltage
ms 0 3200 1000
J12 Errorhandling
0 = no fault acknowled-
gement necessary;
255 = fault acknowled-
gement necessary;
768 = no fault acknowled-
gement + fault
report about diag-
nosis;
1023 = fault acknowledge-
ment + fault report
about diagnosis
768
J8
Min supply voltage
supervision
Adjustment of the minimal supply voltage:
Below this supply voltage the valve switches off with an error message.
J9
Relay time out off range
min supply voltage
Adjustment of the runtime monitoring:
The supply voltage must be at least constantly before the valve is
ready for operation.
J12
Errorhandling
Adjustment of the fault response or report:
0 = no fault acknowledgement necessary
255 = fault acknowledgement necessary
768 = no fault acknowledgement + Fault report about diagnosis
1023 = fault acknowledgement + Fault report about diagnosis
Overview for additional expert mode parameters
Individual description of additional expert parameters

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker D Series and is the answer not in the manual?

Parker D Series Specifications

General IconGeneral
BrandParker
ModelD Series
CategoryControl Unit
LanguageEnglish

Related product manuals