PEERLESS SERIES 62 - Steam Header, Risers and Equalizer Sizing; Steam Supply and Return Piping; Hot Water Supply and Return Piping

PEERLESS SERIES 62
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table1: SteamHeader,Risersand EqualizerSizing
L---RETURN
SUGGESTEDPIPING
t t
ETURN
NOTE:Thereturnfrom systemshouldalwaysenterequalizer
throughHartfordLoop,approximately2"- 4" below
normalwaterline.
Steamheadershouldbe24" rain.aboveboilernormal
waterline.
Figure16: SteamSupplyand ReturnPiping
Model No.Supply Size of Header Equalizer
No. Outlets Outlets Supply Size
6t-03 1 2" -- 1114"
61-04 1 2" -- 11/4"
61-05 1 2" -- lr_"
61-06 2 2" 21_" 11_"
61-07 2 2" 2+/2" 11_"
61-08 2 2" 3" 11_"
62-09 2 2" 3" 11_"
62-10 2 2" 3" 1!_"
62-11 2 2" 3" 1_"
62-12 3 2" 31_" 11_"
62-13 3 2" 31_" 11_"
62-14 3 2" 31_" tl_"
62-15 3 2" 31_" 11_"
STEAM BOILER
SUGGESTEDPIPING
HOT WATERBOILER
_TOP w_STt ¥_LV[ (Nomwl_eJrY O_J_W_
Cu_{D _to _ [xF_l_,_ TANK
_ S_T_II_ESS v,_Tl_ ;_'_1_ is _ _Fw°_ ;4(ATW4G<
Figure 17: Hot Water Supply and Return Piping
11