www.pegasustech.com.br 9
TECHNICAL FEATURES
The following table indicates the main technical characteristics of the equipment.
Nominal output current
10 A
Forced output current for 1 minute
12,5 A
Fuse for protection of the power supply
10 A / 300 V
Vad trimpot adjustable sensing voltage range
E1 160 Vca à 300 Vca
E2 330 Vca à 600 Vca
Frequency of operation in the sensing voltage range
50 Hz ou 60 Hz
Generator voltage measuring range
0 à 840Vca
Generator minimum voltage for pre-excitation
5 Vca
Minimum generator frequency for control
22 Hz
Rated operating voltage (power)
220Vca
Power supply range (3 e E3/4)
50 à 280Vca (up to 300Vca in transient)
Frequency of operation of the power supply (Power)
50Hz ou 60Hz
Power fluctuation voltage (Power)
±30%
Maximum input power
1350VA
Power consumption (by equipment)
~13VA
Power connection
Single phase
Sensing voltage connection
Single phase
Rectifier gain ratio controlled (no load)
0,45
Maximum field voltage
135Vcc
Static regulation
< 0,5%
Limiter U/F
Adjusted to 54Hz or 45Hz
Dinamic response adjustable by trimpot Stb
8 à 500ms
Working temperature range
-40°C à 60°C
Storage temperature range
-20°C à 40°C
Maximum relative humidity
(operation and storage)
0 80%
Pollution degree
3
Protection degree
IP00
Operation altitude
Less than 2000m or greater equal to 2000m
EMI suppression
Differential EMI filter class X2
Alarm signaling
Indication of the alarms on the RGB LED
Regulator LED OK
LED RGB Green flashing and 5V lit indicates OK status
Approximate weight
350g +/-10g
Analog input
± 10Vcc
Analog input variation
Variation: +/-15% of the reference voltage
Digital input variation
CW com UP e DW / ±10% of the reference voltage
Parallel operation - Droop
TC PAR/5A ou PAR/1A
Droop
Ranging de 0 à 10 % of the reference voltage
Protections
Generator overvoltage.
Generator over current excitation
Generator over current
Rotating diode failure
Lack of sensing voltage at the startup
Limiters
Thermal excitation limit (Excitation current)
U/F
Lack of sensing voltage in operation
Alarms
Maximum shot angle
µController failure
Resin
Polyurethane anti-flame (V0)
Base
Non-flammable cast aluminum (V0)
Relay (protection alarm)
NF Ok | NA On protection
(10A 250VCA/125VCA/24VCC)
Table 1 - Technical characteristics of the Regulator