ECP200 BASE 2/4
Page 18
USE AND MAINTENANCE MANUAL
Rev. 01-09
SWITCHING ON THE ECP200 BASE ELECTRONIC CONTROLLER
After wiring the electronic controller correctly, power up at 230 V AC; the display panel will
immediately emit a beep and all the LEDs will come on simultaneously for a few seconds.
COMPRESSOR ACTIVATION/DEACTIVATION CONDITIONS
The ECP200 BASE controller activates the compressor when cold room temperature
exceeds setting+differential (r0); it deactivates the compressor when cold room
temperature is lower than the setting.
MANUAL DEFROSTING
To defrost just press the dedicated key (see section 5.2) to activate the elements relay.
Defrosting will not take place if the end-of-defrost temperature setting (d2) is lower than
the temperature detected by the evaporator sensor. Defrosting ends when the end-of-
defrost temperature (d2) or maximum defrost time (d3) is reached.