MAINTENANCE INTERVENTION FREQUENCY
To verify there are not water losses internally the humidifier. after 1 hour of working
To verify electrical connections clamping. after 4 weeks of working
To verify there are not water losses internally the humidifier.
To verify the cylinder state, to remove incrustations and deposits if
present.
To replace the cylinder if necessary.
monthly or every
500 hours of working
To verify cylinder electrodes consumption and the absence of
deformations or darkening on their surface; to replace the cylinder if
worn and torn and if it shows manifets faults.
quarterly or every
1000 hours of working
To replace the cylinder.
To verify electrical connections clamping and water and steam
connections good state.
yearly or every
2500 hours of working
To verify there are not water losses internally the humidifier.
To verify cylinder state, to verify electrodes consumption, to remove
incrustations and deposits if present and to replace the cylinder if
necessary.
with alarm code E1
To verify there are not water losses internally the humidifier.
To verify that the solenoid valve is not disconnected or broken and to
replace it if necessary.
with alarm code E3
To verify that the drain pump is not disconnected or broken and to
replace it if necessary.
If present to remove incidental obstructions on cylinder bottom and/or
in draining pipes.
with alarm code E5 or E6