USER MANUAL
CHANGING THE CYLINDER
The only part of the humidifier subject to wear is the electrode cylinder. This wears
according to how much the machine is used or it is not possible to remove the internal
incrustations.
The EASYSTEAM range features stainless steel electrodes to maximise durability: however,
durability will largely depend on the quality of the water (conductivity and hardness) and on how
much the machine is used.
When the electrodes are worn the water level will rise excessively and trip the maximum level
alarm E1 several times: the cylinder must, at this point, be replaced.
Once you have checked that this alarm does not have other causes (see Chap. 6 – Troubleshooting)
change the cylinder. Proceed as follows:
NEVER CHANGE THE CYLINDER WITH THE MACHINE HOT AND WITH
WATER INSIDE IT. EMPTY ALL THE WATER FROM THE CYLINDER USING
THE MANUAL DISCHARGE KEY FIRST! IT IS COMPULSORY TO FOLLOW
THE INSTRUCTIONS REPORTED AT CHAPTER 7.2.
1. Open the humidifier by removing the front cover as indicated on page 14 (on OEM models this
is not necessary).
2. Unhook the frontal retainer spring from the upper steam flange and slide it off (Fig. 27, 28, and
29).
Fig. 27 Fig. 28 Fig. 29