PelPro Cast Pellet Stove • 7093-600 • 07/13/16pelprostoves.com 11
Installing Your Stove
45° elbow is equivalent to 1 foot of straight pipe
90° elbow is equivalent to 3 feet of straight pipe
Installing Your Stove
Notice:
These are guidelines for successful venting of
your pellet appliance. The more vertical rise
you can obtain in your system, the better it will
perform. Horizontal vent runs can accumulate
ash and will need to be cleaned more often.
Try to keep them as short as possible.
Venting Your Stove
The maximum horizontal venting allowed with no vertical
venting attached is 48 inches including one 90° elbow
or two 45° elbows. Addition of any horizontal venting
beyond 48 inches requires a minimum 60 inches of
additional vertical vent. Horizontal sections of vent pipe
should have a 1/4 inch rise per foot. We recommend
using the shortest venting and fewest elbows possible
when venting horizontal.
We recommend the use of 4 inch vent with any
installation requiring more than two 90° elbows, or more
than 15 feet of venting.
Minimum Vertical Vent for One Elbow
0
5
10
15
20
0 5 10 15 20
Horizontal Run, (ft)
Minimum Vertical Rise
(ft)
Horizontal Run (FT)
Minimum Vertical Vent for One Elbow
0
5
10
15
20
0 5 10 15
Minimum Vertical
Rise, (ft)
Minimum Vertical Vent for Two Elbows
Length of Horizontal Sections (FT)
0
5
10
15
20
25
0246 8 10 12
Minimum Vertical Rise
(ft)
Minimum Vertical Vent for Three Elbows
Length of Horizontal Sections (FT)
ONE 90° ELBOW
Total
Horizontal
Minimum
Vertical
Vent
Diameter
403
553
663
773
884
994
10 10 4
11 11 4
12 12 4
13 13 4
14 14 4
15 15 4
16 16 4
17 17 4
18 18 4
19 19 4
TWO 90° ELBOWS
Total
Horizontal
Minimum
Vertical
Vent
Diameter
253
363
473
583
693
7 10 4
8 11 4
9 12 4
10 13 4
11 14 4
12 15 4
13 16 4
14 17 4
15 18 4
THREE 90° ELBOWS
Total
Horizontal
Minimum
Vertical
Vent
Diameter
2 11 4
3 12 4
4 13 4
5 14 4
6 15 4
7 16 4
8 17 4
9 18 4
10 19 4
11 20 4
WARNING!
Fire Risk.
Only LISTED venting
components may be
used
NO OTHER vent components may be used.
Substitute or damaged vent components
may impair safe operation.