SENSOR PROBE INSTALLATION (FIG. A AND FIG. B)
1. Do not install sensor probes in tank sensor ports before loading tank with gravel and/or resin.
Sensor probes could be damaged by falling gravel and/or resin during loading. (Reference
“5800 XTR2 Enhanced with AccuSense™ Technology Top 3 Tips for Success” for tips on
application suggestions.)
2. Load sensor resin tank with distributor tube, gravel and/or resin per your normal loading
procedure. Dry loading is preferred as some water will exit the tank through the sensor ports
without probes installed.
3. Please note that the sensor probe with the longest wire must be installed in the lower tank
sensor port.
4. Use a clean cloth to remove any debris (resin, etc.) from the tank bulkheads (sensor tank
ports, Fig. A.)
5. Apply 100% silicone lubricant (included) to each O-ring and install in the O-ring groove on the
end of each probe. NOTE: Be careful not to get silicone on the gold-plated sensor probe pins as
this could affect sensor conductivity readings.
6. The probe assemblies are keyed for easy alignment; align probe pins to pin holes in the tank,
and push each probe into the tank bulkhead.
7. Install the red probe retainer clips into bulkhead. Ensure that each clip is fully seated
in the bulkhead.
8. Plug sensor wire harness into appropriate circuit board receptacle, Fig. B.
9. Connect white end of sensor wire harness to white end of the sensor probe assembly.
10. Install probe cover included with tank.
FLECK
5800 XTR2
ENHANCED WITH ACCUSENSE™ TECHNOLOGY
Installation Guide
1
2
3
ONE OF THE FOLLOWING FLECK 5800 XTR2 VALVES:
PN 580008-009 Set up for 8” tanks
PN 580008-010 Set up for 9” or 10” tanks
PN 580008-011 Set up for 12” tanks
This installation guide augments the 5800 XTR2 Service Manual (PN 43359-02).
The Fleck XTR2 Electronic Control now features AccuSense sensor technology capability as of software version 4.0.
For a complete installation, the following components are required:
1
ONE OF THE FOLLOWING STRUCTURAL POLYGLASS TANKS:
PN CH34204-03010201-30 0844 PG 2.5"T UI BLK 9100 SNSRTK COMP BASE
PN CH34205-03010201-30 0948 PG 2.5"T UI BLK 9100 SNSRTK COMP BASE
PN CH34206-03010201-30 1054 PG 2.5"T UI BLK 9100 SNSRTK COMP BASE
PN CH34299-03010201-30 1248 PG 2.5"T UI BLK 9100 SNSRTK COMP BASE
2
ONE PENTAIR ACCUSENSE SENSOR PROBE ASSEMBLY
PN 61893 KIT, SENSOR PROBE ASSEMBLY
3

Other manuals for Pentair FLECK 5800 XTR2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pentair FLECK 5800 XTR2 and is the answer not in the manual?

Pentair FLECK 5800 XTR2 Specifications

General IconGeneral
BrandPentair
ModelFLECK 5800 XTR2
CategoryController
LanguageEnglish

Related product manuals