30
HART Multiplexer System KFD*-HM*-16
Commissioning
Factory Setting
5.2.3 LED Indication
The device is equipped with three LEDs which are located on the front of the housing.
The LEDs have the following meanings:
LED indication during the initialization process
LED indication during the scanning process
Faulty LED indication during commissioning
DIP switch 1 2 3 4 5 6 7 8 Meaning
Position Off Off Off Off Off Off Off Off Manufacturer test disabled,
baud rate 9600 baud
RS-485 address 0
Table 5.4
Note!
In the factory setting, the address 0 is set. Ensure that you do not assign any addresses more
than once.
Color Meaning
Red Fault indication, detected during the initialization process
Green Operating indication
Orange HART communication with a field device
Table 5.5
Color Status Meaning
Red Off Initialization process
Green Flashes
Orange Off
Table 5.6
Color Status Meaning
Red Off Scanning process
Green Lit
Orange Flashes
Table 5.7
Note!
For further information about the scanning process, see chapter 5.2.4.
Color Status Meaning
Red Flashes If all three LEDs flash one after the other, DIP switch 1 (test) is in
the on position. Turn the switch to off and repeat commissioning.
Green Flashes
Orange Flashes
Table 5.8