2013-06
22
VBP-HH1-V3.0*
Error messages
7 Error messages
The following messages can appear in the addressing device display.
Erro r
code
Meaning Description Remedy
F1 AS-Interface overload Current consumption of
the AS-Interface slaves
connected to the
addressing device is too
high.
Connect an external
power supply.
F2 Slave not found No AS-Interface slave
has been found at the
active address
Check the address or
connect an AS-Interface
slave.
F3 Programming error When programming the
address or the IDI code,
the value could not be
permanently stored in
the AS-Interface slaveās
EEPROM.
If necessary, repeat the
programming.
F4 Target address
occupied
The target address, to
which the current AS-
Interface slave is to be
re pro grammed , i s
occupied.
Assign a different
address to the active
AS-Interface slave.
F5 Address 0 occupied Address 0 is occupied
by another AS-Interface
slave
Make sure that address
0 is not occupied.
F6 Standard AS -In te r fac e
slave found instead of
the A/B-Slave
The standard operation
cannot be executed
because the active AS-
Interface slave does not
satisfy the specification
2.1
You cannot use the
Read IO, Set slave
parameters, and
Read/write slave data
operating modes with
the currently connected
standard AS-Interface
slave.
F7 A-/B slave found
instead of the standard
AS-Interface slave
The active standard AS-
interface slave has been
replaced by an A-/B
slave
Assign an address to
the A-/B-Slave in the
corresponding address
area A or B.
F8 Reception error Due to a fault, the AS-
Interface slave
response could not be
correctly received
Carry out the action
again.