6.7 Set Slave Parameter operating mode
In the operating mode Read/write slave data, the slave parameter value
activates the data transmission from the addressing device to the AS-Interface
slave. The standard value is 15 for standard AS-Interface slaves and 7 for A/B
slaves.
The set data value is retained until:
You change the active address in the Addressing operating mode,
You replace the AS-Interface slaves which have the same address but
different ID, ID2, or IO codes.
The addressing device is automatically switched off or man ually switched
off after a long period without use.
You must adapt the corresponding slave parameters according to the AS-
Interface slave used.
Set parameters
1. Set the desired slave parameter value with the and buttons.
By scrolling up and down, the RDdisplay goes out.
2. Press the button.
WRappears in the operating mode display. The parameter value is
temporarily accepted, but not transferred to the slave.
6.8 Read/write Slave Data operating mode
Setting and sending output data
1. Set the desired output data value using the and buttons.
The RD display goes out when scrolling.
2. To temporarily save the desired output data value and transmit it once to the
active AS-Interface slave, briefly press the button. If you want to execute a
cyclic output data exchange, you must (for security reasons) press and hold
the button. The output data value is cyclically transmitted to the AS-
Interface slave until you release the button.
WRappears in the operating mode display.
The ou tput data value is 0 as standard.
PRG
button is pressed briefly
Send previously set output data once to an AS-Interface
slave/display set output data
button pressed and held
Cyclic sending of previously set output data
button is pressed briefly
Read out input data once from the AS-Interface slave and
send previously set output data to the AS-Interface slave.
button pressed for 2
seconds.
Cyclic reading o f the input data, cyclic sending of
previously set output data.
PRG
PRG
ADR
ADR
PRG
PRG