Semiconductor outputs 774434 774435 774438
Conditional rated short cir-
cuit current 100 A 100 A 100 A
Lowest operating current 0 mA 0 mA 0 mA
Utilisation category in ac-
cordance with EN
60947-1 DC-12 DC-12 DC-12
Relay outputs 774434 774435 774438
Number of output con-
tacts
Safety contacts (N/O),
instantaneous 3 3 3
Auxiliary contacts (N/C) 1 1 1
Max. short circuit current
IK 1 kA 1 kA 1 kA
Utilisation category
in accordance with the
standard EN 60947-4-1 EN 60947-4-1 EN 60947-4-1
Utilisation category of
safety contacts
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 5 A 5 A 5 A
Max. power 1250 VA 1250 VA 1250 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 5 A 5 A 5 A
Max. power 125 W 125 W 125 W
Utilisation category of
auxiliary contacts
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 2 A 2 A 2 A
Max. power 500 VA 500 VA 500 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 2 A 2 A 2 A
Max. power 50 W 50 W 50 W
Utilisation category
in accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Utilisation category of
safety contacts
AC15 at 230 V 230 V 230 V
Max. current 2,5 A 2,5 A 2,5 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 1,5 A 1,5 A 1,5 A