PNOZ 8
Operating Manual PNOZ 8
22152-EN-05
| 9
Function Description
The safety relay PNOZ 8 provides a safety-oriented interruption of a safety circuit. When
supply voltage is supplied the "POWER" LED is lit. The unit is ready for operation when the
feedback loop Y1-Y2 and the start circuit S12-Y1 are closed.
} Input circuit is closed (e.g. E-STOP pushbutton not operated):
Safety contacts 13-14, 23-24 and 33-34 are closed, auxiliary contact 41-42 is open.
The unit is active.
The LEDs "CH.1" and "CH.2" are lit.
A high signal is present at the semiconductor output switch state Y32.
} Input circuit is opened (e.g. E-STOP pushbutton operated):
Safety contacts 13-14, 23-24 and 33-34 are opened redundantly, auxiliary contact
41-42 is closed.
The LEDs "CH.1" and "CH.2" go out.
A low signal is present at the semiconductor output switch state Y32.
Semiconductor output fault Y35
} A low signal is present at semiconductor output Y35 if the supply voltage is present and
the internal fuse (circuit breaker) has not blown. If there is a fault on the safety relay, a
high signal is present at Y35, the "FAULT" LED lights. Once the cause of the fault has
been removed, the fuse must be reset via the reset pushbutton.
Operating modes
} Single-channel operation: No redundancy in the input circuit, earth faults in the start and
input circuit are detected.
} Dual-channel operation with detection of shorts across contacts: Redundant input circuit,
PNOZ 8 detects
earth faults in the start and input circuit,
short circuits in the input circuit,
shorts across contacts in the input circuit.
} Dual-channel operation without detection of shorts across contacts: Redundant input cir-
cuit, detects PNOZ 8
earth faults in the start and input circuit,
short circuits in the input circuit.
} Automatic start: Unit is active once the input circuit has been closed.
} Manual start: Unit is active once the input circuit and the start circuit are closed.
} Monitored start: Unit is active once
the input circuit is closed and then the start circuit is closed and opened again.
the start circuit is closed and then opened again once the input circuit is closed.
} Increase in the number of available contacts by connecting contact expandsion modules
or external contactors/relays.