Permitted operating height
The values stated in the technical details apply to the use of the device in operating heights
up to max. 2000 m above sea level. When used in greater heights, constraints have to be
taken into account:
} Permitted maximum operating height 5000 m
} Reduction of rated insulation voltage and rated impulse withstand voltage for applica-
tions with safe separation:
Maximum operation
height
Rated insulation
voltage Overvoltage category
Max. rated impulse
withstand voltage
3000 m 150 V II 2.5 kV
100 V III 2.5 kV
4000 m 150 V II 2.5 kV
100 V III 2.5 kV
5000 m 100 V II 1.5 kV
24 V III 0.8 kV
} Reduction of rated insulation voltage and rated impulse withstand voltage for applica-
tions with basic insulation:
Maximum operation
height Rated insulation voltage Overvoltage category
Max. rated impulse
withstand voltage
3000 m 250 V II 2.5 kV
150 V III 2.5 kV
4000 m 250 V II 2.5 kV
150 V III 2.5 kV
5000 m 150 V II 1.5 kV
100 V III 1.5 kV
} From an operating height of 2000 m the max. permitted ambient temperature is re-
duced by 0.5 °C/100 m
Operating height Permitted ambient temperature
3000 m 50 °C
4000 m 45 °C
5000 m 40 °C