PNOZ s4.1
Operating Manual PNOZ s4.1
21890-EN-15
| 8
Unit features
} Positive-guided relay outputs:
– 3 safety contacts (N/O), instantaneous
– 1 auxiliary contact (N/C), instantaneous
} 1 semiconductor output
} Connection options for:
– E-STOP pushbuttons
– Safety gate limit switches
– Start buttons
– Light grids and safety switches
– PSEN
– Safety valves for furnaces
} A connector can be used to connect 1 PNOZsigma contact expansion module
} Operating modes can be set via rotary switch
} LED indicator for:
– Supply voltage
– Input status, channel1
– Input status, channel2
– Switch status of the safety contacts
– Start circuit
– Errors
} Plug-in connection terminals (either spring-loaded terminal or screw terminal)
} See order reference for unit types
Safety features
The safety relay meets the following safety requirements:
} The circuit is redundant with built-in self-monitoring.
} The safety function remains effective in the case of a component failure.
} The correct opening and closing of the safety function relays is tested automatically in
each on-off cycle.