PNOZ X9
Operating Manual PNOZ X9
19526-EN-09
25
Conventional thermal current
while loading several contacts
774606 774609
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 8 A 8 A
Conv. therm. current with 2 con-
tacts 5,6 A 5,6 A
Conv. therm. current with 3 con-
tacts 4,6 A 4,6 A
Conv. therm. current with 4 con-
tacts 4 A 4 A
Conv. therm. current with 5 con-
tacts 3,5 A 3,5 A
Conv. therm. current with 6 con-
tacts 3,2 A 3,2 A
Conv. therm. current with 7 con-
tacts 3 A 3 A
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 8 A 8 A
Conv. therm. current with 2 con-
tacts 8 A 8 A
Conv. therm. current with 3 con-
tacts 8 A 8 A
Conv. therm. current with 4 con-
tacts 7 A 7 A
Conv. therm. current with 5 con-
tacts 6 A 6 A
Conv. therm. current with 6 con-
tacts 5,5 A 5,5 A
Conv. therm. current with 7 con-
tacts
5 A 5 A
Times 774606 774609
Switch-on delay
With automatic start typ. 200 ms 200 ms
With automatic start max. 250 ms 250 ms
With automatic start after power
on typ. 220 ms 220 ms
With automatic start after power
on max. 300 ms 300 ms
With manual start typ. 200 ms 200 ms
With manual start max. 250 ms 250 ms
With monitored start typ. 150 ms 150 ms
With monitored start max. 220 ms 220 ms