PNOZ X9P
Operating Manual PNOZ X9P
1003362-EN-12
| 11
Timing diagram
Out semi OUT
Out semi ON
[2] [3]
[1]
Legend
} Power: Supply voltage
} Start: Start circuit
} Input: Input circuit
} Output safe: Safety contacts
} Output aux: Auxiliary contacts
} Out semi ON: Semiconductor output supply voltage
} Out semi OUT: Semiconductor output switch state
} [1]: Automatic start
} [2]: Manual start
} [3]: Monitored start
} a: Input circuit closes before start circuit
} b: Start circuit closes before input circuit
} t
1
: Switch-on delay
} t
2
: Delay-on de-energisation
} t
3
: Recovery time
Installation
} The unit should be installed in a control cabinet with a protection type of at least IP54.
} Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).
} When installed vertically: Secure the unit by using a fixing element (e.g. retaining bracket
or end angle).