Wiring
Operating Manual PSENvip RL D P Set
1001641-EN-09
| 59
6.2 Connections
6.2.1 Receiver
The top of the receiver has two 8-pin M12 connectors.
X1
X2
Fig.: M12 connector on the receiver
The receiver is connected via two 8-pin cables.
1
2
3
4
8
5
6
7
Fig.: Receiver's pin assignment
The cable ends of the Pilz ready-made cable are colour-coded. Please refer to the tables
below for the coding details.
Pin assignment of M12 connector X1 on the receiver
PIn No. Designation Description Colour
1 Activate *) Output: Start communication with
safety system
White
2 24 VDC Input, 24 VDC supply voltage Brown
3 Protected field mode 1 Input, setting of protected field modes Green
Tool class PLC ->
PSENvip Bit 1 *)
Input, safety system reflects tool class
Bit 1
4 Protected field mode 2 Input, setting of protected field modes Yellow
Tool class PLC ->
PSENvip Bit 2 *)
Input, safety system reflects tool class
Bit 2
5 OSSD1 Output, OSSD1 Grey
6 Mute1 Output, dynamic muting Pink
Tool class PSENvip ->
PLC Bit 1 *)
Output, sends tool class Bit 1 to safety
system
7 0 V Input, 0 V supply voltage Blue
8 TRM_ON Output, signal to switch the transmit-
ter's light source on and off
Red