Diagnostics and Troubleshooting
Operating Manual PSENvip RL D P Set
1001641-EN-09
| 91
9.1.2 Major errors
Possible causes
} Serious internal error
} Wiring error, short across contacts, short circuit
} No valid tool data
} Overrun not entered
} Fault on the optical system
Reaction of the PSENvip
} The PSENvip switches to a STOP state.
} Outputs OSSD1/OSSD2 on the receiver are switched off.
} In this state, operation is no longer possible. However, diagnostics are available.
Remedy
} Note the error message (see section entitled "Error messages").
} Rectify the error.
} Restart the PSENvip: Switch supply voltage off and then on again.
9.1.3 Fatal errors
Possible causes
} Major system defect
} Error during self-test
Reaction of the PSENvip
} The PSENvip switches to a FATAL state. It remains in a safe condition.
} Outputs OSSD1/OSSD2 on the receiver are switched off.
} The transmitter's light source goes out.
} In this state, operation is no longer possible. The display is no longer operable. Dia-
gnostics are no longer available.
Remedy
} It is not possible for the user to rectify the error.
} Note the conditions under which the error occurred.
} Restart the PSENvip: Switch supply voltage off and then on again.
} The error message will not be displayed. However, it will be possible to select the DIA-
GNOSTICS menu.
} Note the error message (see section entitled "Error messages").
} Contact Pilz.