PZE X4.1P
Operating Manual PZE X4.1P
1003203-EN-09
| 13
Inputs 777587 787587
Max. overall cable resistance Rl-
max
Single-channel at UB DC 30 Ohm 30 Ohm
Dual-channel without detection
of shorts across contacts at UB
DC 60 Ohm 60 Ohm
Relay outputs 777587 787587
Number of output contacts
Safety contacts (N/O), instant-
aneous 4 4
Max. short circuit current IK 1 kA 1 kA
Utilisation category
In accordance with the standard EN 60947-4-1 EN 60947-4-1
Utilisation category of safety con-
tacts
AC1 at 240 V 240 V
Min. current 0,01 A 0,01 A
Max. current 6 A 6 A
Max. power 1500 VA 1500 VA
DC1 at 24 V 24 V
Min. current 0,01 A 0,01 A
Max. current 6 A 6 A
Max. power 150 W 150 W
Utilisation category
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Utilisation category of safety con-
tacts
AC15 at 230 V 230 V
Max. current 3 A 3 A
DC13 (6 cycles/min) at 24 V 24 V
Max. current 4 A 4 A
Utilisation category in accordance
with UL
Voltage 250 V AC G.U. (same polarity) 250 V AC G.U. (same polarity)
With current 6 A 6 A
Voltage 24 V DC G. U. 24 V DC G. U.
With current 6 A 6 A
Pilot Duty B300, R300 B300, R300
External contact fuse protection,
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Max. melting integral 66 A²s 66 A²s
Blow-out fuse, quick 6 A 6 A
Blow-out fuse, slow 4 A 4 A
Blow-out fuse, gG 6 A 6 A
Circuit breaker 24V AC/DC,
characteristic B/C 4 A 4 A