PZE X4.1P
Operating Manual PZE X4.1P
1003203-EN-09
| 14
Relay outputs 777587 787587
Contact material AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au
Conventional thermal current
while loading several contacts
777587 787587
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 6 A 6 A
Conv. therm. current with 2 con-
tacts 6 A 6 A
Conv. therm. current with 3 con-
tacts 4,5 A 4,5 A
Conv. therm. current with 4 con-
tacts 3,5 A 3,5 A
Times 777587 787587
Switch-on delay
With automatic start typ. 15 ms 15 ms
With automatic start max. 20 ms 20 ms
With automatic start after power
on typ. 15 ms 15 ms
With automatic start after power
on max. 30 ms 30 ms
Delay-on de-energisation
With E-STOP typ. 10 ms 10 ms
With E-STOP max. 20 ms 20 ms
With power failure typ. 60 ms 60 ms
With power failure max. 80 ms 80 ms
Supply interruption before de-ener-
gisation in the input circuit 2 ms 2 ms
Supply interruption before de-ener-
gisation 20 ms 20 ms
Environmental data 777587 787587
Climatic suitability EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C -10 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during operation Not permitted Not permitted
EMC EN 60947-5-1, EN 61000-6-2, EN
61326-3-1
EN 60947-5-1, EN 61000-6-2, EN
61326-3-1
Vibration
In accordance with the standard EN 60068-2-6 EN 60068-2-6
Frequency 10 - 55 Hz 10 - 55 Hz
Amplitude 0,35 mm 0,35 mm