EasyManua.ls Logo

Pixsys ATR 421 - Page 47

Pixsys ATR 421
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ATR 421 - User manual 47
73 coo. f. Cooling Fluid: De nes cooling  uid type.
ai r > Default
oi L
H2o
74 p. b . m . Proportional Band Multiplier:
1.005.00. > Default: 1.00.
75 ov.d.b. Overlap/Dead Band:
-20.0%…50.0%. > Default: 0.0%.
76 co.c.t. Cooling Cycle Time:
1…300 secondi. > Default: 10s.
77 rem .s. Remote Setpoint: Selects remote setpoint mode, through
serial communication.
di s . (Disabled). Controller operates autonomously. > Default.
sLve (Slave). Controller is a slave normally in STOP: goes in RUN when,
on master device connected to the serial, a cycle is started.
mstr (Master). Controller transmits the setpoint to all controllers
connected to the serial and set as slave.
78 bd.rt. Baud Rate: Selects baud rate for serial communication.
4.8 k 4800 bit/s
9.6 k 9600 bit/s 38.4k 38400 bit/s
19.2k 19200 bit/s > Default 57.6k 57600 bit/s
28.8k 28800 bit/s 11 5 . 2 11520 0 bit/s
79 se.p.s. Serial Parameters Setting: Selects data format for serial
communication.
8. n .1 8 data bits, no parity, 1 stop bit. > Default.
8. o .1 8 data bits, odd parity, 1 stop bit.
8. e.1 8 data bits, even parity, 1 stop bit.
80 sL. ad. Slave Address: Selects slave address for serial communication.
1…254 Address for slave functioning. > Default: 254.

Table of Contents

Related product manuals