81 se.de. Serial Delay: Select serial delay.
0…100 ms. > Default: 20ms.
82 c. fLt. Conversion Filter: Adc  lter: number of means on analogue-
digital conversion.
1…15 samplings > Default: 10.
83 v.fLt. Visualization Filter:
di s . (Disabled)
ptcH (Pitchfork  lter) > Default.
fi . o r. (First Order)
f. o r. p. (First Order with Pitchfork)
2. s . m . (2 Samples Mean)
3. s . m . (3 Samples Mean)
4. s . m . (4 Samples Mean)
5. s . m. (5 Samples Mean)
6. s. m. (6 Samples Mean)
7. s . m . (7 Samples Mean)
8. s. m. (8 Samples Mean)
9. s . m . (9 Samples Mean)
10.s. m . (10 Samples Mean)
84 retr. Retransmission: Retransmission for analogue output.
Parameters 86 and 87 de ne upper/lower limit of scale
di s . (Disabled). > Default.
c.s pu . (Command Setpoint) Retransmit the command setpoint.
pro. (Process) Retransmit the process.
85 re, tY. Retransmission Type: Select retransmission signal type.
0-10 (0…10V)
0-20 (0…20mA)
4-20 (4…20mA) > Default.
86 Lo .L. r. Lower Limit Retransmission: Lower limit analogue output
range.
-999…+9999 [digit
10
] (degrees.tenths for temperature sensors).
> Default: 0.