User manual - ATR227 - 13
8.1 Loading default values
This procedure allows to restore factory settings of the device.
Press Display Do
1
SET
for 3 sec.
Display 1 shows

with
the 1st digit ashing, while
display 2 shows
3$66
2
or
Modify the ashing digit
and move to the next one
pressing
SET
.
Enter password

.
3
SET
to conrm
The device loads default
settings.
Turn o and restart the
device.
9 Table of Conguration Parameters
The parameters list below can be entered by passwords 1234 (for standard) and 5678
(for advanced). Enter password 1357 to access the complete list.
1 6(1 Sensor (Password 1234)
Analogue input conguration
7F.
Tc-K (Default) -260 °C..1360 °C
7FV
Tc-S -40 °C..1760 °C
7FU
Tc-R -40 °C..1760 °C
7FM
Tc-J -200 °C..1200 °C
7FW
Tc-T -260 °C..400 °C
7F(
Tc-E -260 °C..980 °C
7FQ
Tc-N -260 °C..1280 °C
7FE
Tc-B 100 °C..1820 °C
3W
Pt100 -100 °C..600 °C
3W
Pt100 -100 °C..140 °C
QL
Ni100 -60 °C..180 °C
QWF
NTC10K -40 °C..125 °C
3WF
PTC1K -50 °C..150 °C
3WV
Pt500 -100 °C..600 °C
3WN
Pt1000 -100 °C..600 °C
2
G3 Decimal Point (Password 1234)
Select number of displayed decimal points

Default

1 Decimal
3
GH*U Degree (Password 1234)
Select degree type
aF
Celsius (Default)
aI
Fahrenheit