No. Display Description Range
20 State of led OUT2 for
relevant contact
: ON with open
contact
: ON with
closed contact
21 Alarms hysteresis -999…+999 digit
(if temperature: digit is
1/10 °C)
22 Protection of set2
Operator may not
change value of setpoint
2
: access to set
2 enabled
: access to set
2 desabled
23 Software filter
Filter set to 1 means
sampling 15Hz
1-17 no. of averages.
24 Select type of
autotuning (automatic
rating of PID parameters)
Function is activated only
if process value is at
least 35% lower than
setpoint
: desabled
: automatic
rating of parameters at
starting or when
setpoint is changed
: function is
started manually
25 Soft start 0 disabled
1-1000 units/hour
(°C/hour if temperature)
26 Hold time for
programmed cycle
0-1440 minutes