5.1.4 Damper RPM Setting
AirTouch 4 can work with other dampers which are not made by Polyaire. But the
damper motors have to meet certain requirements:
Power supply: 24 VAC
Drive Open and Drive Close
Revolution per Minute (RPM): 0.1 to 2.5
5.1.5 Installer Settings Password
The password is used to prevent unauthorized changing of the installer settings.
To reset this password, touch the password edit eld in the ‘Parameter’ screen,
and then type in the new password and touch ‘Enter’ key to conrm the password
change.
5.1.6 Reset and Save current system settings
To record all system settings, press Save Settings to File button. After the settings
have been saved successfully, it will be stored on the console in the name of
AtchV4_Setting_Id.txt. Please transfer the settings le to a micro SD card or send
it to an email address for permanent storage in case the console is unaccessible.
Use File Manager on the console to access the le under
/storage/emulated/0/airtouch.
If the main module has been replaced, the system can be recovered from this le.
After the settings le is stored under the folder /storage/emulated/0/airtouch,
press the Recover Saved Settings button to recover.
After successful recovery, the system has to be powered o for at least 30
seconds and then powered back on to use the recovered settings.
If the system needs to be reset to factory default settings in some cases, press
Reset to Factory. All group names and settings will be back to original factory
settings.