5. Loosen the screw connections of the gas connection pipe at the mixing channel
and the gas valve
6. Remove the gas connection pipe (2) and the gas jet (3)
7. Loosen the gas connection pipe at the gas valve (4) and remove gas valve (5)
8. Loosen the 5 fastening screws at the mixing channel/heat exchanger
9. Remove (6) bracket
10. Remove intake muffler
11. Pull out the burner together with mixing channel and fan to the front (7)
12. Clean burner pipe with soft brush
Caution: Use new seals!
When re-fitting, new gaskets should be used, particularly for the the gas connect-
ing pipe.
10.5 Protection against contact
Danger of electric shock! To ensure shock-proof protection, all parts of the device
to be screwed on, have to be screwed on correctly; especially the cover parts!
Maintenance
128 Paramount three 30-115 kW 7308272-03 03.14