3.2 Specification
Tab. 2: Specification
Model Paramount three 30 40 60 80 95 115
Product-ID-No. CE-0085BL0514
VDE-Reg.-No. VDE-mark
International protection IPx4D
Gas category II
2H3+
Device categories B
23
, B
33
, C
13X
, C
33X
, C
43X
, C
53
, C
63X
, C
83
Nominal heat input
range
Natural
Gas
Heating
mode
kW 5,6-30,0 9,0-38,0 14,0-58,0 21,0-77,0 20,0-95,0 25,0-115,0
Nominal heat out-
put range
Natural
Gas
80/60°C kW 5,4-29,2 8,7-36,8 13,4-56,3 20,3-74,7 19,4-92,2 24,3-111,7
50/30°C kW 6,0-31,3 9,6-39,0 14,9-60,1 22,6-79,7 21,4-98,1 26,7-118,6
Standard efficiency
(DIN 4702)
75/60°C 106,0 106,0 106,0 106,0 106,0 106,0
40/30°C 109,0 109,0 109,0 109,0 109,0 109,0
pH-value condensate - 4-5 4-5 4-5 4-5 4-5 4-5
Volume condensate 40/30°C l/h 0,83-3,00 1,19-2,84 1,78-4,71 2,53-6,46 2,75-8,42 3,85-9,61
NO
X
-Standard emission factor mg/
kWh
17 20 20 20 25 25
CO-Standard emission factor mg/
kWh
5 10 10 10 20 20
Data for design of the chimney to EN 13384 (room sealed operation)
Exhaust gas tem-
perature (full load)
Full load 80/60°C °C 66 75 71 73 73 77
Low load °C 53 56 59 59 59 60
Full load 50/30°C °C 46 53 54 54 51 56
Low load °C 33 35 34 35 32 33
Exhaust gas mass
flow
Natural
Gas
80/60°C g/s 2,8-14,8 4,4-18,7 6,9-28,5 10,3-37,9 9,8-46,7 12,3-56,6
50/30°C g/s 2,5-14,1 4,1-18,0 6,4-27,4 9,7-36,4 9,1-44,8 11,3-54,4
Exhaust gas mass
flow
Propane 80/60°C g/s 2,6-14,1 4,2-17,8 6,6-27,2 9,8-36,1 14,1-44,6 16,4-53,9
50/30°C g/s 2,4-13,4 3,9-17,1 6,1-26,1 9,2-34,6 13,3-42,6 15,4-51,7
CO2-content
natural gas
Natural
Gas
% 8,3 - 8,8
CO2-content LPG Propane % 10,3 - 10,7
Draft requirement mbar 0
Max. delivery pressure at exhaust gas out-
let
mbar 1,1 1,1 1,1 1,1 1,5 1.8
Exhaust gas/air supply connection mm 80/125 110/160
Exhaust gas value group to DVGW G636 - G6
Technical Data Paramount Three 30-115
7308272-03 03.14 Paramount three 30-115 kW 13