Function Prog.
no.
Level
1)
Standard value
Frost protection setpoint 1314 Eu 10.0°C
Heating curve slope 1320 Eu 1.50
Heating curve displacement 1321 E 0.0 °C
Heating curve adaption
Off | On
1326 E Off
Summer/winter heating limit 1330 Eu 18°C
24-hour heating limit 1332 E 0 °C
Flow temp setpoint min 1340 E 8°C
Flow temp setpoint max 1341 E 80°C
Flow temp setpoint room stat 1342 E --- °C
Delayed heat request 1346 E 0 s
Room influence 1350 C - - - %
Room temp limitation 1360 E 0.5°C
Boost heating 1370 E --- °C
Quick setback
Off | Down to reduced setpoint | Down to frost prot setpoint
1380 E Down to reduced set-
point
Optimum start control max 1390 E 0 min
Optimum stop control max 1391 E 0 min
Reduced setp increase start 1400 E --- °C
Reduced setp increase end 1401 E -15°C
Continuous pump operation
No | Yes
1409 E No
Overtemp prot pump circuit
Off | On
1420 E Off
Mixing valve boost 1430 E 5°C
Actuator running time 1434 E 120 s
Floor curing function
Off | Functional heating | Curing heating | Functional/curing heating |
Curing/Functional heating | Manually
1450 E Off
Floor curing setp manually 1451 E 25°C
Floor curing setp current 1455 E 0 °C
Floor curing day current 1456 E 0
Excess heat draw
Off | Heating mode | Always
1461 E Heating mode
With prim contr/system pump
No | Yes
1472 E yes
Pump speed reduction
Operating level | Characteristic
1480 E Characteristic
Pump speed min 1482 C 30 %
Pump speed max 1483 C 80 %
Curve readj at 50% speed 1488 E 10 %
Flow setp readj speed ctrl
No | Yes
1490 E No
Operating level changeover
Frost protection | Reduced | Comfort
1498 E Reduced
Programming
7308272-03 03.14 Paramount three 30-115 kW 57